KEVIN MCGILL, Associated Press
NEW ORLEANS (AP) — An electrical device that had been installed expressly to prevent a power outage caused the Super Bowl blackout, the stadium’s power company said Friday as it took the blame for the outage that brought the game to a halt for more than a half-hour.
Officials of Entergy New Orleans, a subsidiary of New Orleans-based Entergy Corp., said the device, called a relay, had been installed in switching gear to protect the Superdome from a cable failure between the company’s incoming power line and lines that run into the stadium.
The switching gear is housed in a building known as “the vault” near the stadium that receives a line directly from a nearby Entergy power substation. Once the line reaches the vault, it splits into two cables that go into the Superdome.
Company officials said the device performed with no problems during January’s Sugar Bowl and other earlier events, but has been removed and will be replaced. All systems at the Superdome are now working and the dome will host a major Mardi Gras event Saturday night, said Doug Thornton, an executive with SMG, the company that manages the stadium for the state.
The power failure at Sunday’s big game cut lights to about half of the stadium for 34 minutes, halting play between the Baltimore Ravens and San Francisco 49ers.
The FBI had ruled out cyberterrorism as a cause.
Entergy’s announcement came shortly before officials appeared before a committee of the City Council, which is the regulatory body for the company, to answer questions about the outage.
Entergy New Orleans CEO Charles Rice and Dennis Dawsey, an Entergy vice president for distribution, told the Council that SMG agrees the cause of the outage was a relay failure. Asked if the two corporations still plan to hire a third-party investigator, Rice said that possibility remains open.
Committee member Jackie Clarkson pressed for such an independent probe. “We’ve told the public we’re going to have an outside investigation,” she said.
“We’ll work closely with SMG and if there is a need for a third-party investigation, we will do that,” Rice said.
It remains unclear whether the problem with the relay was a design flaw or a manufacturing problem. Rice said Entergy is working with the manufacturer.
“I’m pleased that we were able to find the root cause,” Thornton said.
Shabab Mehraeen, an assistant professor of electrical engineering at Louisiana State University, said the relay device is a common electrical fixture in businesses and massive facilities such as the Superdome.
“They are designed to keep a problem they sense from becoming something bigger, like a fire or catastrophic event,” said Mehraeen, who holds a doctorate from the Missouri University of Science and Technology in Rolla, Mo.
The devices vary in size, and while Mehraeen noted he was not familiar with the specifics of the relay at the Superdome, he added, “I wouldn’t be surprised if it was bigger than a truck.”
Mehraeen said the reasons the devices fail are the subject of much academic research into the interaction of relays with the complex electrical systems they regulate.
“It’s not unusual for them to have problems,” he said. “They can be unpredictable despite national testing standards recommended by manufacturers.”
Entergy and SMG had both upgraded lines and equipment in the months leading up to the Super Bowl. Rice said the new switching gear, with the faulty relay, was installed as part of a $4.2 million upgrade by Entergy, including the installation of a new power line dedicated solely to the stadium.
In a separate project, SMG replaced lines coming into the stadium after managers expressed concerns the Superdome might be vulnerable to a power failure like the one that struck Candlestick Park during a 49ers Monday Night Football game in 2011. That outage was blamed at least partly on a transformer explosion.
Thornton stressed Friday that the dome was drawing only about two-thirds of its power capacity Super Bowl night, and said typical NFL games in late August or September can draw a little more.
City officials had worried that the Super Bowl outage might harm New Orleans’ chances of getting another NFL championship game.
But NFL Commissioner Roger Goodell downplayed that possibility after the outage, saying the NFL planned to keep New Orleans in its Super Bowl plans. Mayor Mitch Landrieu said the city intends to bid for the Super Bowl in 2018.
Copyright 2013 The Associated Press.
Read the rest of the Top 20 list here:
#20 Crescent Electric Acquires Lake Electric Supply – March 5, 2013
#19 Reports: Copper Delivery Prices Soar – May 31, 2013
#18 Blog: WESCO Outlook – August 13, 2013
#17 Graybar achieves near-record profitability in 2012 – March 15, 2013
#16 Blog: Wesco’s Strategies For Growth – November 13, 2013
#15 Blog: Siemens shareholders approve Osram spin off – January 25, 2013
#14 Blog: Acquisitions fueled distributors’ growth in 2012 – March 4, 2013
#13 Southwire Introduces Electrician’s Tools – July 18, 2013
#12 Southwire Announces Organizational Changes – January 22, 2013
#11 2013 tED Magazine Best Of The Best Awards – August 7, 2013
#10 Blog: Amazon, Google Supply Update – August 30, 2013
#9 WSJ: Copper supply concerns – April 15, 2013
#8 Huge copper theft bust in Arizona valued at $10 million – May 6, 2013
#7 NAW speaker predicts strong economy, copper inflation for 2013 – January 30, 2013
#6 Leff Electric Acquired by AMP Electric – October 2, 2013
#5 Southwire to roll out new cable pull technology – March 12, 2013
#4 Super Bowl blackout traced to preventive equipment – February 8, 2013
#3 tED magazine 2013 30 Under 35 List – June 4, 2013
#2 Eaton executive outlines company’s future with Cooper – January 8, 2013
Tagged with tED